AGAP    
 
   
Pumps Various according to pump model
- please contact our technical office for details
Cistern Polypropylene
Valve Brass with Plastic Float
Base Powder Coated Mild Steel
Fittings Brass
   
Idromat Housing Nylon
Membrane Nitrile
Sensor Brass

 

Construction  
 18 or 68 Ltr tank with air-gap supplying water to one of our pumps controlled by our Idromat regulation device equipped with flow and pressure sensor connected to an electronic system all mounted on a base.
 
Applications
• For non-domestic quality water.
• To prevent backflow contamination of mains water.
• Whilst maintaining flow and pressure.
Operating conditions
BT61E, BTm61E,
BT70E, BTm70E

Liquid temperature from -10 °C to +90 °C.
Ambient temperature up to 40 °C.
Total suction lift up to 7 m.
Continuous duty.

MXH203E, MXHm203E,
MXH204E, MXHm204E,
MXH205E, MXHm205E,

Liquid temperature from - 15 °C to + 110 °C.
Ambient temperature up to 40 °C.
Maximum permissible pressure in the pump casing: 10 bar.
Continuous duty.

Motor
Various depending on pump selection
See Pump specifications

BT61E, BTm61E,
BT70E, BTm70E

MXH203E, MXHm203E,
MXH204E, MXHm204E,
MXH205E, MXHm205E,
 

Special Systems
In addition to the standard range AGAP systems shown we can also provide special packages to specification, incorporating other pumps or booster set packages from our production. Units are complete with control systems and one-piece or modular storage tanks to current legislation.

Please contact our technical sales office for further details.

Warranty
One year (as per our standard terms and conditions of sale)
  Performance Data  
 
3Phase 230 400 1Phase 230   Q                      
  A A   A kW m3/hr 0.38 0.48 0.6 0.75 1 1.2 1.5 1.89 2.4 3 3.6
BT61E 1.9 1.1 BTm61E 2.5 0.33 H(m) 38 36 34 31 28 24 19 12 5    
BT70E 3.7 2.2 BTm70E 6 0.75   59 57 55 51 48 43 38 30 22 10
 
 
3Phase 230 400 1Phase 230 P1 P2 Q                  
  A A   A kW kW m3/hr 0 1 1.5 2 2.5 3 3.5 4 4.25
MXH203E 2.4 1.4 MXHm203E 3 0.65 0.6 H(m) 33 31 29 27 24 21 18 14 12
MXH204E 2.8 1.6 MXHm204E 4.2 0.9 0.75 45 42 40 37 34 30 25 21 18
MXH205E 3.5 2 MXHm205E 5.4 1.2 1 57 53 50 47 43 38 32 26 23
 
  Installation Data
All electrical connections should be made as per fig.1. DO NOT SWITCH ON POWER SUPPLY UNTIL INSTALLATION PIPE-WORK IS MADE AND CISTERN IS FULL OF WATER.
Fig.2 refers
A Water outlet 1" BSPm
B Cistern Water Supply
C Warning Pipe - 22mm compression. Note the purpose of this connection is to warn of a potential cistern overflow condition. We therefore advise that the pipe-work from the overflow should be located so as to visually alert personnel should overflow occur.
D Optional wall mount brackets. We advise the brackets be fixed to the wall with 6mm wall bolts. Mark holes as per template. The AGAP system is then attached to the brackets with 4 x M6 bolts via the holes and hank bushes provided. Wall mount brackets are only available for BT61EAGAP118 and BT61EAGAP318 systems

IMPORTANT - The main weir E is provided to meet with the type AB air gap requirements. It is important that this overflow is never restricted. It is also important to consider the implications of water spilling through the weir/s - keep away from electrical installations or other sensitive areas

IDROMAT OPERATION - The Idromat flow and pressure controller is fitted to operate the pump automatically on demand. Once installation is complete, switch on the power supply. Assuming the discharge line is closed the pump will run for a short period to fill the system. Open the discharge line slowly to establish flow and release air. If flow is not quickly established depress the reset button F for a few seconds, if still no flow is present you may need to prime the pump (see pump instructions). Remove plug G, release air, reconnect the power and repeat above procedure.

Note: The Idromat will provide dry running protection should the cistern empty. Do not restart the Idromat until the cistern is full. You may need to press the reset button F.

System Status

H Power On (Green Light) - Discharge line closed, pump idle, system pressurised.
I On (Yellow Light) - Discharge line open, pump running
J Failure (Red Light) - If no flow within 8 secs following start-up, Idromat will recognise lack of water or closed discharge and stop pump. Reset F may be required

NOTES - For cold water use only. We advise the installation of a throttling valve after the Idromat discharge
to facilitate control. It is important that the outgoing flow from the pump does not exceed the incoming flow
to the cistern.

 

 
  Electrical Connection (fig.1)
Single Phase Supply via fused spur (by other) to Idromat controller. (See instruction manual)

IF IN DOUBT CONSULT A QUALIFIED ELECTRICIAN
Three phase systems must be used in conjunction with our control box. The Idromat controller should only be connected to a 230V single phase supply. Max. FLC for Idromat is 10A, Max starting Current is 25A

 

 
   
   
   
  DIMENSIONS  
  BT61EAGAP118 and BT61EAGAP318  
   
  BT70EAGAP168 and BT70EAGAP368  
   
  MXH203EAGAP168 and MXH203EAGAP368
MXH204EAGAP168 and MXH204EAGAP368
MXH205EAGAP168 and MXH205EAGAP368
 
   
  Special Systems