NCD Three speeds circulating twin pumps with flanges    
 
   
  Construction  
Pump casing with suction and delivery connections diameter and on the same axis (in-line).
Materials:  
Pump casing Cast iron
Impeller Stainless steel
Shaft Stainless steel
Applications
For clean liquids, without abrasives, which are non-aggressive for the pump materials (contents of solids up to 0.2%).
For heating, conditioning, cooling and circulation plants.
For civil and industrial applications.
When low noise operation is required.
Motor
2-4-pole induction motor, 50 Hz.
Three adjustable speeds.
NCD: three-phase 230V or 400 V.
NCDM: single-phase 230 V.
Insulation class F.
Protection IP 43.
Operating conditions
Liquid temperature from -10 °C to +120 °C (in short-time duty up to + 140 °C).
Ambient temperature up to 40 °C.
Maximum glycol quantity: 50% (Mixture with more than 20% glycol content require rechecking of the pumping data).
Maximum permissible working pressure 6/10 bar.

Type

Minimum suction pressure: bar

Temperature
50°C 80°C 110°C

NCD 40

0,05 0,8 1,4
NCD 50 0,3  1 1,6
NCD 65 0,3 1 1,6

NCD 80

0,3 1 1,6

 

Warranty
One year (as per our general sales conditions).
 

  Characteristic Curves, dimensions and weights  
   
   
     
  NCD 40  
   
   
  NCDM 40  
   
 

 
  NCD 50  
   
   
  NCDM 50  
   
 

 
  NCD 65  
   
   
  NCD 80